Manual
60 Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012
Appendix A Specifications
Environmental
Specifications
The 1732E ArmorBlock Thermocouple and RTD Input Modules have the
following environmental specifications.
Certifications
The 1732E ArmorBlock Thermocouple and RTD Input Modules have the
following certifications.
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Temperature, ambient, max 60 °C (140 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±3 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on signal ports
±3 kV @ 5 kHz on communication ports
Surge transient immunity IEC 61000-4-5:
±2 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±500V line-line (DM) and ±1 kV line-earth (CM) on signal ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from150 kHz…80 MHz
Enclosure type rating Meets IP65/66/67/69K (when marked)