Manual
Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 59
Specifications Appendix A
Data format 16-bit sign magnitude
Sensors supported 100…200 Ω α=0.00385/0.003916 Pt RTD
100/120 Ω Ni RTD
10 Ω Cu α =0.00427 RTD
Sensor Types 100
Ω
Pt 385
200
Ω
Pt 385
100
Ω
Pt 3916
200
Ω
Pt 3916
10
Ω
Cu 427
120
Ω
Ni 672
100
Ω
Ni 618
120
Ω
Ni 618
Input range RTD type Temperature
Range (°C)
Voltage
Range
100
Ω
Pt 385 0…390.48 Ω -200…850 °C 0…156.25 mV
200
Ω
Pt 385 0…781 Ω -200…850 °C 0…312.5 mV
100
Ω
Pt 3916 0…337.03 Ω -200…630 °C 0…156.25 mV
200
Ω
Pt 3916 0…674.06 Ω -200…630 °C 0…312.5 mV
10
Ω
Cu 427 0…19.116 Ω -320…500 °C 0…19.53 mV
120
Ω
Ni 672 0…445.10 Ω -70…445 °C 0…156.25 mV
100
Ω
Ni 618 0…198.88 Ω -60…180 °C 0…78.125 mV
120
Ω
Ni 618 0…238.65 Ω -90…140 °C 0…78.125mV
Input resistance 0…1000 Ω 300 mV, 5 mW
Accuracy 0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature
30 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration Factory calibrated. Calibration is also supported through
RSLogix 5000.
Sample Rate Filters
(1)
50 Hz
60 Hz
250 Hz
500 Hz
Common Mode Rejection
Ratio
120 dB @ 50/60 Hz
Normal Mode Rejection
Ratio
100 dB @ 50/60 Hz
(1) Sample rate filter selectable on a module basis only.
Input Specifications – 1732E-IR4IM12R
Attributes Value