Manual

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012 49
Calibrate Your Modules Chapter 5
Calibrate the RTD Module
The 1732E-IR4IM12R does not calibrate for voltage or current. It uses two
precision resistors to calibrate the channels in ohms. The module has a preset
calibration points for the sensor type configured for each input channel,
Perform the calibration process through the RSLogix 5000 software.
While you are online, you must access the Calibration tab on the Module
Properties dialog box. See Edit Your Module Configuration
on page 21.
1. Click Calibration Tab on the Module Properties dialog box.
2. Check the Calibrate checkbox to specify which channel to calibrate.
In this example, check Channels 0…3.
3. Under Calibrate Channels select One At a Time.
4. Click Start Calibration, which is active when:
the system is online, and
you selected at least one of the channels.
Calibration Points for the RTD Module
RTD Sensor Type Calibration Points
Ohms 0 and 500 Ohms
100 Ω Pt 385 0 and 500 Ohms
200 Ω Pt 385 0 and 1000 Ohms
100 Ω Pt 3916 0 and 500 Ohms
200 Ω Pt 3916 0 and 1000 Ohms
10 Ω Cu 427 0 and 64.9 Ohms
120 Ω Ni 672 0 and 500 Ohms
100 Ω Ni 618 0 and 250 Ohms
120 Ω Ni 618 0 and 250 Ohms
Choose whether to calibrate each
channel one at a time or in groups all
at once