Installation Instructions DeviceNet ArmorBlock™ Network Powered 16-input Module Catalog number 1732D-IBDPM12MND, Series A Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 About the Module 4 Catalog Number Explanation 5 Install the Module 5 Set the Node Address 5 Mount the Module 6 Connect the Cordsets 8 Communicate with the Module 9 Interpret Status Indicators 10 Specifications 12
DeviceNet ArmorBlock™ Network Powered 16-input Module Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
DeviceNet ArmorBlock™ Network Powered 16-input Module 3 Environment and Enclosure ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
DeviceNet ArmorBlock™ Network Powered 16-input Module About the Module The DeviceNet 1732D ArmorBlock I/O family consists of standalone 24V DC I/O modules that communicate via the DeviceNet network. The sealed IP67 housing of these modules requires no enclosure. Note that environmental requirements other than IP67 may require an additional appropriate enclosure. I/O connectors are sealed M12-style. The 1732D-IBDPM12MND module is shown here.
DeviceNet ArmorBlock™ Network Powered 16-input Module 5 The DeviceNet network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our web site at www.ab.com/networks for producer/consumer technology information and updates. Catalog Number Explanation The catalog number 1732D-IBDPM12MND refers to a DeviceNet 24V DC 8-port, 16-input mini-style network connector module. Install the Module To install the module: • Set the node address.
DeviceNet ArmorBlock™ Network Powered 16-input Module Node Address Default Setting This example shows the default node address set at 63. 43968 The rotary switches are read periodically. If the switches have been changed since the last time they were read and no longer match the online address, a minor fault occurs, which is indicated by the module indicator flashing red. Settings of 64…99 cause the module to use the last valid node address stored internally.
DeviceNet ArmorBlock™ Network Powered 16-input Module 7 Module Dimensions 65 (2.56) 43.25 (1.70) 26.5 (1.04) Millimeters (inches) D N e t MOD 179 (7.05) NET In I-0 I - 15 I-1 I - 14 I-2 I - 13 I-3 I - 12 I-4 I - 11 I-5 I -10 I-6 I-9 169 (6.
DeviceNet ArmorBlock™ Network Powered 16-input Module Connect the Cordsets The ArmorBlock DeviceNet family has 5-pin micro-style connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cordsets you selected for your module to the appropriate ports. ATTENTION: To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
DeviceNet ArmorBlock™ Network Powered 16-input Module 9 Refer to Cordsets and Field Attachables, publication M117-CA502A, or visit the Connection Devices website, http://www.ab.com/connectionsystems. ATTENTION: Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements. Communicate with the Module This module’s I/O is exchanged with the master through a cyclic, polled, or change-of-state connection.
DeviceNet ArmorBlock™ Network Powered 16-input Module Interpret Status Indicators This module has the following indicators: • Network and module status indicators for DeviceNet • Auxiliary power indicator • Individual I/O status indicators for inputs and outputs 1732D-IBDPM12MND Module status indicator I/O status indicators D N e t MOD Network status indicator NET In I-0 I - 15 I-1 I - 14 I-2 I - 13 I-3 I - 12 I-4 I - 11 I-5 I -10 I-6 I-9 I-7 I-8 0 I/O status indicators 0 2
DeviceNet ArmorBlock™ Network Powered 16-input Module 11 Indicator Status for Modules Module status Status Description Off No power applied to the device. Green Device is online and has one or more I/O connections in established state. Flashing green Device needs commissioning due to missing, incomplete, or incorrect configuration. Red Critical fault – device timed out or has an unrecoverable fault. Flashing red Recoverable fault – input or output short circuit.
DeviceNet ArmorBlock™ Network Powered 16-input Module Specifications General Specifications Attribute Value Number of inputs 16 Input type 61131-2 Type 3 compatible Off-state input voltage, max 5V DC On-state input voltage, min 11V DC On-state input voltage, nom 24V DC On-state input voltage, max 25V DC Sensor source voltage, min 11V DC Sensor source voltage, max 25V DC Off-state input current, max 1.
DeviceNet ArmorBlock™ Network Powered 16-input Module 13 (1) Input Off-to-On or On-to-Off delay is time from a valid input signal to recognition by the module. (2) Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (3) Refer to Connection Systems, publication C116-CA508.
DeviceNet ArmorBlock™ Network Powered 16-input Module Environmental Specifications Attribute Value Surge transient immunity IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports Conducted RF immunity IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz Emissions CISPR 11: Group 1, Class A Certifications Certification (when product is marked)(1) Value c-UL-us UL-listed Industrial Control Equipment, certif
DeviceNet ArmorBlock™ Network Powered 16-input Module 15 Notes: Publication 1732D-IN007B-EN-E - November 2011
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.