14 DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A
Publication
1732D-IN011A-EN-E - April 2009
Module Status
Status Description Recommended action
Off There is no power applied to the
device.
Apply power to the device.
Green Device is operating normally. None.
Flashing
Green
Device needs commissioning due to
missing, incomplete, or incorrect
configuration.
Check your configuration and cycle
power.
Flashing Red Recoverable fault – input or output
short circuit.
Check your input devices and
check your output devices and
cycle power.
Red Critical fault – device timed out or
has an unrecoverable fault.
Cycle power to the device. If that
does not fix the fault, contact your
Rockwell Automation
representative. The device may
need to be replaced.
Auxiliary Status
Status Description Recommended action
Off There is no auxiliary power applied
to the device.
Apply auxiliary power to the
device.
Green There is auxiliary power applied to
the device.
None.
I/O Status
Status Description Recommended action
Off Output is not energized or input is
not valid.
None.
Yellow Output is energized or input is valid. None.