Indicator Status Description
Network
status
Off Device is not online.
- Device has not completed dup_MAC-id test.
- Device not powered – check module status indicator.
Green Device operating normally and is online with
connections in the established state. As a Group 2
module, it means that the module is allocated to a
master.
Flashing green Device is online with no connections in the established
state.
Red Critical link failure – failed communications module.
Flashing red Recoverable fault – an I/O connection has timed out.
Module
status
Off No power applied to the device.
Green Device is operating normally.
Flashing green Device needs commissioning due to missing,
incomplete, or incorrect configuration.
Flashing red Recoverable fault – input or output short circuit.
Red Critical fault – Device timed out or has an
unrecoverable fault.
I/O status Off Output is not energized or input is not valid.
Yellow Output is energized or input is valid.