Installation Instructions DeviceNet ArmorBlock Network Powered 8-input/8-output Module Catalog Number 1732D-8I8O1212D Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 3 About the Module 4 Install the Module 5 Mount the Module 6 Communicate with Your Module 11 Interpret the Status Indicators 12 Specifications 14
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 3 Environment and Enclosure ATTENTION This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 meters (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module About the Module The DeviceNet 1732D ArmorBlock I/O family consists of stand-alone 24V DC I/O modules that communicate via the DeviceNet network. The sealed IP69K housing of these modules requires no enclosure. Note that it is possible that environmental requirements other than IP69K require an additional appropriate enclosure. I/O connectors are sealed M12 style.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 5 Catalog Number Explanation The catalog number 1732D-8I8O1212D identifies a DeviceNet 24V DC 8-port, with one input and one output per port, 8-input 8-output 0.5 A M12-style network connector module. Install the Module To install the module: • Set the node address • Mount the module • Connect the cord sets Set the Node Address Valid node addresses are 00 through 63.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module To reset the node address: 1. Rotate the switches using a small blade screwdriver. 2. Line up the small black dot on the switch with the number setting you wish to use. 3. Cycle power. Example shows default node address set at 63. 43968 The rotary switches are read periodically.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 7 Product Dimensions Refer to the mounting dimensions illustration to help you mount the module. Module Dimensions 65 mm (2.56 in.) 43.25 mm (1.70 in.) 26.5 mm (1.04 in.) DNet In DNet Out MOD NET I-0 I-7 O-0 O-7 I-1 I-6 O-1 O-6 I-2 I-5 O-2 O-5 I-6 I-4 O-3 O-4 179 mm (7.05 in.) 169 mm (6.64 in.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Mounting the Module in High Vibration Areas If you mount the module in an area that is subject to shock or vibration, we recommend that you use a flat and a lock washer to mount the module. Mount the flat and the lock washer as shown in the mounting illustration. Torque the mounting screws to 0.64 Nm (6 in-lb).
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 9 Connect the I/O Cord Sets to the Module The ArmorBlock DeviceNet family has 5-pin micro-style connectors. We provide caps to cover the unused connectors on your module. Connect the quick-disconnect cord sets that you selected for your module to the appropriate ports. Network Connector Refer to the pinout diagram for the network connector.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Refer to publication M116-CA001 for Rockwell Automation cable and cord set offerings or access the Connection Systems website at http://www.ab.com/sensors/products/connection_systems/. ATTENTION ATTENTION If any I/O devices connected to this equipment require Class 2 power to operate, this equipment and all connected I/O must be powered by a Class 2 source.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 11 Communicate with Your Module This module’s I/O is exchanged with the master through a cyclic, polled, or change-of-state connection. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. Polled - a master initiates communication by sending its polled I/O message to the module. The module consumes the message, updates outputs, and produces a response.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Interpret the Status Indicators This module has the following indicators: • Network status indicator for DeviceNet • Module status indicator for DeviceNet • Individual I/O status indicators for inputs and outputs DNet In Module status indicator I/O status indicators DNet Out MOD Network status indicator NET I-0 I-7 O-0 O-7 I-1 I-6 O-1 O-6 I-2 I-5 O-2 O-5 I-6 I-4 O-3 O-4 0 I/O status indicators 0 2 8 8 6 4 X10 2
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 13 Indicator Status Description Network status Off Device is not online. - Device has not completed dup_MAC-id test. - Device not powered – check module status indicator. Green Device operating normally and is online with connections in the established state. As a Group 2 module, it means that the module is allocated to a master. Flashing green Device is online with no connections in the established state.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Specifications DeviceNet 1732 ArmorBlock Network Powered 8-input/8-output Module, Series A - 1732D-8I8O1212D Inputs Attribute Value Number of inputs 8 Off-state input voltage, max 5V DC On-state input voltage, max 25V DC On-state input voltage, nom 24V DC On-state input voltage, min 11V DC Sensor source voltage, max 25V DC Sensor source voltage, min 11V DC Off-state input current, max 1.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 15 DeviceNet 1732 ArmorBlock Network Powered 8-input/8-output Module, Series A - 1732D-8I8O1212D Outputs Attribute Value Number of outputs 8 On-state output voltage drop, max 0.5V DC Off-peak blocking voltage, min 25V DC On-state output voltage, max 25V DC On-state output voltage, min 11V DC On-state output voltage, nom 24V DC On-state output current, max 0.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module General Specifications Attribute Value Power consumption 2.2 W Power dissipation 11.
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 17 Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F) Temperature, non-operating IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): -45…
DeviceNet ArmorBlock Network Powered 8-input/8-output Module Environmental Specifications (Continued) Attribute Value EFT/B immunity IEC 61000-4-4: ±3 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communications ports Surge transient immunity IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports ±2 kV line-earth(CM) on communications ports Conducted RF IEC 61000-4-6: 10V rms with 1 kHz s
DeviceNet ArmorBlock Network Powered 8-input/8-output Module 19 Certifications Certification (when Value product is marked)(1) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.