Chapter 2 Installation Instructions
Wire the Ground Connection
The system can have up to three separate ground systems:
An AC Safety Ground (sometimes called the ‘dirty ground’) to protect
you in the event of a fault. The ground stud on the adapter base unit must
be connected to the AC safety ground, along with all exposed metalwork,
such as DIN rails.
An Instrument Ground (sometimes called the ‘clean ground’ or ‘OV DC
ground’) to provide a good stable OV reverence for the system. Every
signal return must be referenced to the instrument ground, which is
isolated from the AC Safety Ground.
Some field wiring needs shielded (screened) cable. There can be a Shield
Ground in addition to the AC Safety and Instrument Grounds to provide
a common point to terminate cable shields.
Connect the adapter base unit ground stud to the AC safety ground bus bar of
the system:
Use an M6 lug on the end of the ground wire.
Place the lug below the second nut on the ground stud between two
washers and use two 10 mm (.039 in.) wrenches to tighten the nuts.
Use a minimum conductor wire size of 4 mm
2
(10 AWG).
Figure 29 - Adapter Base Unit Ground Connection Detail
MP-PWR-24V1
OV
MP-PWR-24V2
OV
32125-M
AC Ground Connection Only