I/O Termination Assemblies
I/O termination assemblies are inserted into the I/O base units. There are eight
types of termination assemblies (two for each module) depending on the
architecture of your system and the I/O modules you are going to use.
Digital Input Termination Assemblies
Digital input termination assemblies support these features:
16-channel simplex TA provides termination for 16 digital input channels
Industry-standard field device connections at terminal blocks
24V DC digital input channels with a load of 5.11 k
per input channel
Individually fused channels with over voltage input protection
There are two types of digital input termination assemblies:
A 1715-TASIB16D, 16-channel simplex TA that provides termination for
16 digital input channels and mates with a single 1715-IB16D digital
input module
A 1715-TADIB16D, 16-channel duplex TA that provides termination for
16 digital input channels and mates with up to two 1715-IB16D digital
input modules
Table 6 - I/O Termination Assembly Descriptions
I/O Module Termination Assembly Cat. No. Termination Assembly Description
1715-IB16D 1715-TASIB16D Digital input simplex
1715-TADIB16D Digital input duplex
1715-OB8DE 1715-TAS0B8DE Digital output simplex
1715-TADOB8DE Digital output duplex
1715-IF16 1715-TASIF16 Analog input simplex
1715-TADIF16 Analog input duplex
1715-OF8I 1715-TASOF8 Analog output simplex
1715-TADOF8 Analog output duplex