User Manual Owner manual
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 311
I/O Tag Definitions Appendix G
Data REAL Input data
Faults DINT, bit-field Channel fault status:
Bit Name Description
0 Fault 0 = Good
1 = Circuit fault for this channel
1 ModAFault 0 = Good
1 = This channel on Module A is faulted/
failed
2 ModBFault 0 = Good
1 = This channel on Module B is faulted/
failed
3 Underrange 0 = Good
1 = Underrange detected
4 Overrange 0 = Good
1 = Overrange detected
RollingTimestamp INT Timestamp data
Status DINT, bit-field Bit Name Description
0 ModAFault 0 = Good
1 = Fault or module not present
1 ModBFault 0 = Good
1 = Fault or module not present
8 GroupFault 0 = Good
1 = Any channel on module is faulted/
failed
9 ModAGroupFault 0 = Good
1 = Any channel on Module A is faulted/
failed
10 ModBGroupFault 0 = Good
1 = Any channel on ModuleB is faulted/
failed
Table 83 - 16-channel Analog Input, Duplex, Input
Tag Name Data Type Definition