User Manual Owner manual

Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 307
I/O Tag Definitions Appendix G
1715-IB16D
CIPConnections DINT Total number of active CIP connections
CIPLostPackets DINT Total of all CIP packets
TCP Connections DINT Total of all TCP connections
CUPUtilization DINT Echo of Connection Manager object CPU_Utilization attribute
Table 76 - Input
Tag Name Data Type Definition
Table 77 - 16-channel Digital Input, Simplex
Tag Name Data Type Definition
Fault DINT, Binary Module fault bit: 0 when a module is present and reporting valid data, OxFFF_FFFF when no module is
present, no Logix connection exists, or reported data is valid
Data INT Input state, one bit per channel for channels 0…15:
0 = Off/de-energized
1 = On, energized
Status DINT, bit-field Redundancy and power status:
Bit Name Description
8 GroupFault 0 = Good
1 = Any channel or module faulted/failed
PtFault INT Channel fault status; one bit per channel for channels 0…15:
0 = Normal
1 = Channel is faulted/failed
Open Wire INT Open wire diagnostic status; one bit per channel for channels 0…15:
0 = Normal
1 = Indicates open wire detected
ShortCircuit INT Short circuit diagnostic status; one bit per channel for channels 0 …15:
0 = Normal
1 = Indicates short circuit detected
Indeterminate INT Indeterminate diagnostic status; one channel per channel for channels 0…15:
0 = Normal
1 = Indicates indeterminate input voltage detected