Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 305
Appendix G
I/O Tag Definitions
1715-AENTR Adapter Module
Table 76 - Input
Tag Name Data Type Definition
Fault DINT, Binary Adapter fault bit: 0 when at least one adapter is present and reporting valid data, OxFFF_FFFF when no adapters
are present, no Logix connection exits, or reported data is invalid.
Status DINT, bit field Adapter redundancy and power status:
Bit 0: ModAFault 0 = good
1 = fault or module not present
Bit 1: ModBFault 0 = good
1 = fault or module not present
Bit 8: Power1Fault 0 = good
1 = fault or module not present
Bit 9: Power2Fault 0 = good
1 = fault or module not present
LinkStatus DINT, bit-field Adapter module Ethernet port status:
Bit 0: PortA1Connected 0= Inactive
1 = Active
Bit 2: PortA2Connected 0= Inactive
1 = Active
Bit 3: PortB1Connected 0= Inactive
1 = Active
Bit 4: PortB2Connected 0= Inactive
1 = Active
FullDuplex DINT, bit-field Adapter module Ethernet port half/full duplex status:
Bit 0: PortA1FullDuplex 0= Inactive
1 = Active
Bit 2: PortA2Duplex 0= Inactive
1 = Active
Bit 3: PortB1Duplex 0= Inactive
1 = Active
Bit 4: PortB2Duplex 0= Inactive
1 = Active