PFD and PFH Calculations for a SIL 2 System Appendix E
The PFD calculations in Table 74 are calculated for a 5-year proof test interval
(43,800 hours) and are specific to1715 I/O components in ControlLogix
systems.
De-energize-to-trip 5-year Proof Test Interval
Table 74 - De-energize-to-trip 5-year Proof Test Interval
MTTR 24 Hours PTI 5.0 Years Simplex Configuration Duplex Configuration
Cat No.
Series
Firmware
Version
Description
MTBF
λs
λdu
λdd
SFF
tce'
HFT
PFHde
PFDde
STR
β
βd
tce'
tge'
HFT
PFHde
PFDde
Arch
STR
1715-
AENTR
A2.001EtherNet
adapter
dual
module
841,973
8.43E-07
9.82E-09
3.34E-07
97.74%
N/A
N/A
N/A
N/A
N/A
1.0%
1.0%
5.44E+02
3.71E+02
1
3.47E-09
2.24E-06
1oo2D
8.43E-08
1715-
IB16D
A 2.001 16-channel
digital
input
module
3,535,791
2.06E-07
6.57E-10
7.60E-08
99.77%
2.12E+02
0
7.48E-10
1.82E-05
2.82E-07
1.0%
0.5%
7.53E+01
5.82E+01
1
4.77E-10
2.13E-06
1oo2D
2.06E-09
1715-
IF16
A 2.001 16-channel
analog
input
module
3,535,791
2.06E-07
6.57E-10
7.60E-08
99.77%
2.12E+02
0
7.48E-10
1.82E-05
2.82E-07
1.0%
0.5%
7.53E+01
5.82E+01
1
4.77E-10
2.13E-06
1oo2D
2.06E-09
1715-
OB8DE
A 2.001 16-channel
digital
output
module
9,677,085
7.94E-08
2.96E-10
2.36E-08
99.26%
2.95E+02
1
7.68E-10
6.97E-06
1.03E-07
1.0%
1.0%
N/A
N/A
1
1.54E-09
1.39E-05
2oo2
7.94E-10
1715-
OF8I
A 2.001 16-channel
analog
output
module
5,446,179
1.34E-07
5.50E-10
4.96E-08
99.51%
2.64E+02
1
9.13E-10
1.33E-05
1.83E-07
1.0%
0.5%
N/A
N/A
1
1.82E-09
2.64E-05
2oo2
1.34E-09