User Manual Owner manual
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 297
PFD and PFH Calculations for a SIL 2 System Appendix E
PFD Calculations with 24-hour MTTR
The PFD calculations in Table 70 are calculated for a 1-year proof test interval
(8760 hours) and are specific to1715 I/O components in ControlLogix systems.
De-energize-to-trip 1-year Proof Test Interval
Table 70 - De-energize-to-trip 1-year Proof Test Interval
MTTR 24 Hours PTI 1.0 Years Simplex Configuration Duplex Configuration
Cat No.
Series
Firmware
Version
Description
MTBF
λs
λdu
λdd
SFF
tce'
HFT
PFHde
PFDde
STR
β
βd
tce'
tge'
HFT
PFHde
PFDde
Arch
STR
1715-
AENTR
A2.001EtherNet
adapter
dual
module
841,973
8.43E-07
9.82E-09
3.34E-07
97.74%
N/A
N/A
N/A
N/A
N/A
1.0%
1.0%
1.28E+02
9.34E+01
1
3.45E-09
5.13E-07
1oo2D
8.43E-08
1715-
IB16D
A 2.001 16-
channel
digital
input
module
3,535,791
2.06E-07
6.57E-10
7.60E-08
99.77%
6.16E+01
0
7.48E-10
5.12E-06
2.82E-07
1.0%
0.5%
3.43E+01
3.08E+01
1
4.77E-10
4.36E-07
1oo2D
2.06E-09
1715-
IF16
A 2.001 16-
channel
analog
input
module
3,535,791
2.06E-07
6.57E-10
7.60E-08
99.77%
6.16E+01
0
7.48E-10
5.12E-06
2.82E-07
1.0%
0.5%
3.43E+01
3.08E+01
1
4.77E-10
4.36E-07
1oo2D
2.06E-09
1715-
OB8DE
A 2.001 16-
channel
digital
output
module
9,677,085
7.94E-08
2.96E-10
2.36E-08
99.26%
7.82E+01
1
7.66E-10
1.85E-06
1.03E-07
1.0%
1.0%
N/A
N/A
1
1.53E-09
3.69E-06
2oo2
7.94E-10
1715-
OF8I
A 2.001 16-
channel
analog
output
module
5,446,179
1.34D-07
5.50E-10
4.96E-08
99.51%
7.20E+01
1
8.90E-10
3.61E-06
1.83E-07
1.0%
0.5%
N/A
N/A
1
1.78E-09
7.19E-06
2002
1.34E-09