User Manual Owner manual

292 Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Appendix E PFD and PFH Calculations for a SIL 2 System
Energize-to-action 1-year Proof Test Interval
Table 63 - Energize-to-action 1-year Proof Test Interval
MTTR 10 Hours PTI 1.0 Years Simplex Configuration Duplex Configuration
Cat No.
Series
Firmware
Version
Description
MTBF
λs
λdu
λdd
SFF
tce'
HFT
PFHe
PFDe
STR
β
βd
tce'
tge'
HFT
PFHe
PFDe
Arch
STR
1715-
AENTR
A2.001EtherNet
adapter
dual
module
841,973
7.07E-07
1.67E-08
4.89E-07
93.55%
N/A
N/A
N/A
N/A
N/A
1.0%
1.0%
1.45E+02
1.00E+02
1
5.07E-09
7.84E-07
1oo2D
7.07E-08
1715-
IB16D
A 2.001 16-
channel
digital
input
module
3,535,791
1.88E-07
1.02E-09
1.44E-07
99.30%
4.07E+01
0
1.11E-09
6.31E-06
3.33E-07
1.0%
0.5%
2.35E+01
1.90E+01
1
8.22E-10
4.48E-07
1oo2D
1.88E-09
1715-
IF16
A 2.001 16-
channel
analog
input
module
3,535,791
1.88E-07
1.02E-09
1.44E-07
99.30%
4.07E+01
0
1.11E-09
6.31E-06
3.33E-07
1.0%
0.5%
2.35E+01
1.90E+01
1
8.22E-10
4.48E-07
1oo2D
1.88E-09
1715-
OB8DE
A 2.001 16-
channel
digital
output
module
9,677,085
1.22E-07
8.63E-09
3.53E-07
97.61%
1.15E+02
0
8.63E-09
4.14E-05
4.74E-07
1.0%
1.0%
1.15E+02
7.97E+01
1
3.64E-09
4.16E-07
1oo2
1.22E-09
1715-
OF8I
A 2.001 16-
channel
analog
output
module
5,446,179
3.56E-07
3.32E-08
4.71E-07
93.42%
2.98E+02
0
3.36E-08
1.53E-04
8.27E-07
1.0%
0.5%
2.98E+02
2.02E+02
1
3.23E-09
3.62E-06
1oo2
3.56E-09