1715-IB16D Digital Input Module Diagnostics Appendix C
Closed Switch/On Condition
If SW1 is closed, then current only flows through R2, so to calculate the voltage
present at the input module, use the R2 value of 3.9 kRtotal
Figure 76 - Closed Switch/On Condition
Shield
(if used)
Terminal
Blocks
OV
20Ω
100Ω
50 mA
4.99kΩ
Termination
Assembly
+24V dc
R1
R2
45678
Solution For Voltage
5.1K
SW1
3.9k
15k
Solution For Voltage
45681