Status Indicators Appendix A
Status indicators for the 1715-IF16 analog input module are shown in this table.
Table 57 - Analog Input Module Status Indicators
Indicator State Description
Healthy Steady off No power.
Steady green Module operational - The module has been configured
and is operating without any faults.
Flashing green Standby - The module has not been configured.
Steady red Fault - A fault has been detected on the module.
Ready Steady off No power or no partner module present.
Steady green Synchronized - Synchronized with partner module;
redundant operation.
Run Steady off No power; no backplane communication - No power or
the module is not communicating over the backplane.
Steady green Connected - The module has at least one established
connection.
Flashing green No connections - The module is communicating over the
backplane, but there are no established connections.
Channel 0…7, 8…15 Steady off No signal, no backplane communication - There is no
signal on the channel or the module is not
communicating over the I/O backplane.
Steady amber Signal present - A valid signal has been detected (that is,
measured signal >= 0.4 mA).
Flashing amber Field fault - A field fault has been detected on this
channel.
Steady red Fault - A fault has been detected on this channel.