Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 259
Status Indicators Appendix A
Status indicators for the 1715-OB8DE digital output module are shown in this
table.
Table 56 - Digital Output Module Status Indicators
Indicator State Description
Healthy Steady off No power.
Steady green Module operational - The module has been configured
and is operating without any faults.
Flashing green Standby - The module has not been configured.
Steady red Fault - A fault has been detected on this module.
Ready Steady off No power or no partner module present.
Steady green Synchronized - Synchronized with partner module;
redundant operation.
Run Steady off No power; no backplane communication - No power or
the module is not communicating over the backplane.
Steady green Connected - The module has at least one established
connection.
Flashing green No connections - The module is communicating over the
backplane, but there are no established connections.
Channel 0…7 Steady off Off/de-energized - The channel is off/de-energized.
Steady amber On/energized - The channel is on/energized.
Flashing amber Field fault - A field fault has been detected on this
channel.
Steady red Fault - A fault has been detected on this channel.