User Manual Owner manual

254 Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Appendix A Status Indicators
Rack Status Steady off No power, unlocked - The module has no power or it is not
locked (via the locking screw).
Steady green Rack operational - All modules in the rack are operating
without fault.
Steady red Fault - At least one module in the rack has detected a
fault. Examine the other modules in the rack for their
status indicator condition.
Flashing green/red Self-test - The module is performing its power-on self
tests.
Flashing amber Unlocked - Adapter is unlocked from a previously locked
state.
Unlabeled Status 1
Located directly below Rack Status-used in Recovery
mode
Steady off No power - The module has no power or is not in recovery
mode.
Steady amber Recovery mode - The module is in Recovery mode.
Flashing amber Unlocked - Adapter is unlocked from a previously locked
state.
Unlabeled Status 2
Located directly below Unlabeled Status 1-used in
Recovery mode
Steady off No power - The module has no power or is not in recovery
mode.
Steady amber Recovery mode - The module is in Recovery mode.
Flashing amber Unlocked - Adapter is unlocked from a previously locked
state.
Ethernet 1 and 2 Steady off No power, no link - There is no power or an Ethernet link is
not established.
Steady green Link present - A valid Ethernet link has been established.
Amber Activity - Tx and/or Rx activity is present.
Table 54 Adapter Status Indicators
Indicator State Description