Chapter 6 1715 Redundant I/O System in SIL 2 Safety Applications
Analog Output Modules
The analog output module can be used in applications where the output current
is in the range 4…20 mA during normal operation including trip/action value
and where 0 mA is the fail safe value. In these applications, one 1715-OF8I
output module is sufficient for SIL 2 requirements, two modules provide a 1oo2
level.
The analog output module is rated at SIL 2 as a fail-safe simplex module and
when used in a 1oo2 configuration as a duplex module with these features:
Commanded values and scaling factor
The fail-safe lowest commanded value irrespective of the scaling factor is
0 mA. The application cannot change the scaling factor; it can only be
changed by an online update.
Fail-safe guard band
The fail-safe guard is 1% (0…2 mA) and not user-configurable.
Reaction to Faults
If an output module faults, the following status information is reported:
Module presence
Module health and status
Channel health and status
Field faults
An echo of the front panel indicators for each module
If any of the following internal conditions exist, the output module fails safe:
An internal software error is detected
A power feed combiner over-temperature condition is detected