User Manual Owner manual

190 Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 5 Configure the Redundant I/O System
9. Click OK.
Step 2: Add a 1715-IF16 Analog Input Module in Simplex Mode
Add a new 1715-IF16 Analog Input module in Simplex mode to the project.
1. Add the new module, referring to page 172
.
2. Select the 1715-IF16 module, referring to step 2
on page 187.
The General tab appears.
See Figure on page 174
for General parameter settings.
3. Click Change, referring to Figure on page 188
for Module Definition
parameter settings.
4. Change Redundant to No to place the module in Simplex mode.
5. Click OK.
Low Engineering Enter the Low Engineering value for the channel (between -9999999…99999999). The default is 0.0. Low Signal
and Low Engineering values are shown in pairs.
High Signal Enter the High Signal value for the channel (between 0.0…20.0 mA). The default is 20.0 mA. This value must be
greater than the Low Signal value. High Signal and High Engineering values are shown in pairs.
High Engineering Enter the High Engineering value for the channel (between -9999999…99999999). The default is 100.0. High
Signal and High Engineering values are shown in pairs.
Table 36 - Configuration Parameters for the Analog Input Duplex Module
Parameters Description