User Manual Owner manual
Rockwell Automation Publication 1715-UM001C-EN-P - March 2014 189
Configure the Redundant I/O System Chapter 5
4. Click OK.
5. Click the Connection tab, referring to page 163
.
6. Click the Module Info A tab, referring to page 165
.
7. Click the Module Info B tab, referring to page 165
.
8. Click the Configuration tab.
The Configuration tab appears.
Data Format Display Only.
Redundant Yes indicates Duplex mode.
SIL 2 Safety Choose No if SIL 2 operation is not required.
Choose Yes to enable SIL 2 operation. The safety pull-down menu appears only if using Add-on Profile
version 2.01.007 or later. Two new tabs are available for SIL 2 configuration if you choose Yes. For
information on SIL 2 configuration, see Chapter 6.
Table 35 - Module Definition Parameters for Analog Input Module
Parameters Description
Table 36 - Configuration Parameters for the Analog Input Duplex Module
Parameters Description
Channel Click the channel number to configure parameters for the specified channel (0…15).
Current Range Displays the current range (0…20 mA) for the channel.
This field is read-only.
Low Signal Enter the Low Signal value for the channel (between 0.0…20.0 mA). The default is
4.0 mA. This value must be less than the High Signal value. Low Signal and Low Engineering values are shown in
pairs.