188 Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 5 Configure the Redundant I/O System
The General tab appears.
See Figure on page 174
for detailed parameter information for the
General tab.
3. Click Change.
The Module Definition dialog box appears.
Table 35 - Module Definition Parameters for Analog Input Module
Parameters Description
Series Choose the Series of the module.
Revision Choose the Revision of the module.
For SIL 2 application choose version 3.01.07 or later for 1715 I/O modules.
Electronic Keying Choose the electronic keying you wish to use for the selected module. See Appendix B on page 265
.
Connection Leave as ‘Data’ - Listen Only is not supported.
Input Data Display Only.