User Manual Owner manual

184 Rockwell Automation Publication 1715-UM001C-EN-P - March 2014
Chapter 5 Configure the Redundant I/O System
The Fault/Program Action tab appears.
12. Click OK.
Table 34 - Fault/Program Action Parameters
Parameters Description
Point Click the point number to configure parameters for the specified point (0…7).
Output State During This value Indicates the following controller tag settings
Program mode On
Off
Hold
ProgMode = 0
ProgValue = 1
ProgMode = 0
ProgValue = 0
ProgMode = 1
ProgValue = The value previously set.
Fault mode On
Off
Hold
FaultMode = 0
FaultValue = 1
FaultMode = 0
FaultValue = 0
FaultMode = 1
FaultValue = The value previously set.
Communication Failure If Communication Fail in Program Mode Specify the action to take when communication fail in Program mode. Choose one of the following:
Leave outputs in Program mode state – When selected, lets you maintain outputs in the Program
mode state (default). When cleared, changes outputs to the Fault mode state.
Leave outputs in Program mode state appears dimmed only when in Hard Run mode.
Change outputs to Fault mode state – When selected, lets you change outputs to the Fault mode
state. When cleared, changes outputs to the Program mode state.
Change outputs to Fault mode state appears dimmed only when in Hard Run mode.