18
Parameter
number
Function Basic
value
Setting range Input
V/F characteristics / boost
A41
Boost select 00 00: Man. boost
01: Auto boost
A42
Manual boost 11 0 – 99
A43
Max. boost at % of base frequency 10 0 - 50%
A44
V/F select 00
00: Constant
01: Variable
A45
Maximum output voltage 100 50 - 100%
DC brake
A51
DC Brake active / inactive 00
00: inactive
01: active
A52
DC Brake
Starting frequency
0.5 0.5 – 10 Hz
A53
DC Brake
Waiting time
0.0 0 - 5 s
A54
DC Brake
Braking torque
0 0 - 100%
A55
DC Brake
Braking time
0.0 0 - 60 s
Operating frequency range
A61
Maximum Frequency 0.0 0.5 - 360 Hz
A62
Minimum Frequency 0.0 0.5 - 360 Hz
A63
1
st
Skip Frequency 0 0 - 360 Hz
A64
1
st
Skip Frequency Band 0.5 0 - 10 Hz
A65
2
nd
Skip Frequency 0 0 - 360 Hz
A66
2
nd
Skip Frequency Band 0.5 0 - 10 Hz
A67
3
rd
Skip Frequency 0 0 - 360 Hz
A68
3
rd
Skip Frequency Band 0.5 0 - 10 Hz