User Manual

9
User Configurable Items
Synchronized
Turn-on Delay
0 seconds 0 s
60 s
120 s
180 s
240 s
300 s
360 s
420 s
Specify the time the UPS will wait after the
return of utility power before start-up (to avoid
branch circuit overload).
High Transfer Point 120 V models:
127 VAC
230 V models:
253 VAC
127 VAC
130 VAC
253 VAC
257 VAC
133 VAC
136 VAC
261 VAC
265 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
Low Transfer Point 120 V models:
106 VAC
230 V models:
208 VAC
97 VAC
100 VAC
196 VAC
200 VAC
103 VAC
106 VAC
204 VAC
208 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
The 1609-S350ES ships ready for 230 V
sources. When operating the UPS in 208 V
applications, the UPS low transfer voltage
settings are adjusted through PowerChute
software. The proper setting for low transfer
voltage is 196 V.
Refer to the PowerChute user guide for setting
adjustment details.
Output Voltage
230 V models only 230 VAC 220 VAC
230 VAC
240 VAC
Sets the output voltage of the UPS while
operating on battery.
Function Factory Default User Selectable Choices Description