User Manual User Manual
Rockwell Automation Publication 1608S-UM001A-EN-P - July 2013 13
Installation Chapter 3
Nominal Voltage
Configurations
Table 1 - Nominal Voltage Configurations. (shipped standard with 480V (L-L)
Your Voltage Nominal
Volts per
Channel
Channels Mains
Wires
Wiring
Diagram
(See Table 2)
Power Supply
Jumper JP1
Any single-phase voltage ≤240V nominal 1 2 S1 White wires
100 (L-N for 100/200V split-phase) 100 2 3 S2 White wires
105 (L-N for 105/210V split-phase) 105 2 3 S2 White wires
110 (L-N for 190Y/110V 3-phase) 110 3 4 LN White wires
115 (L-N for 200Y/115V 3-phase) 115 3 4 LN White wires
115 (L-N for 115/230V split-phase) 115 2 3 S2 White wires
120 (L-N for 208Y/120V 3-phase) 120 3 4 LN White wires
120 (L-N for 120/240V split-phase) 120 2 3 S2 White wires
125 (L-N for 216Y/125V 3-phase) 125 3 4 LN White wires
127 (L-N for 220Y/127V 3-phase) 127 3 4 LN White wires
133 (L-N for 230Y/133V 3-phase) 133 3 4 LN White wires
139 (L-N for 240Y/139V 3-phase) 139 3 4 LN White wires
190 (L-L for 190Y/110V 3-phase) 190 3 3 LL White wires
200 (L-L for 100/200V split-phase) 200 1 2 S1 White wires
208 (L-L for 208Y/120V 3-phase) 208 3 3 LL White wires
210 (L-L for 105/210V split-phase) 210 1 2 S1 White wires
216 (L-L for 216Y/125V 3-phase) 216 3 3 LL White wires
220 (L-L for 380Y/220V 3-phase) 220 3 3 LL White wires
230 (L-L for 230Y/133V 3-phase) 230 3 3 LL White wires
230 (L-N for 400Y/230V 3-phase) 230 3 4 LN White wires
240 (L-L for 120/240V split-phase) 240 3 3 LL White wires
240 (L-N for 415Y/240V 3-phase) 240 3 4 LN White wires
254* (L-N for 440Y/254V 3-phase) 254 3 4 LN Red wires
277 (L-N for 480Y/277V 3-phase) 277 3 4 LN Red wires
346 (L-N for 600Y/346V 3-phase) 346 3 4 LN Red wires
346 (L-L for 346Y/200V 3-phase) 346 3 3 LL Red wires
380 (L-L for 380Y/220V 3-phase) 380 3 3 LL Red wires
400 (L-L for 400Y/230V 3-phase) 400 3 3 LL Red wires
400 (L-N for 690Y/400V 3-phase) 400 3 4 LN Red wires
415 (L-L for 415Y/240V 3-phase) 415 3 3 LL Red wires
440 (L-L for 440Y/254V 3-phase) 440 3 3 LL Red wires
440 (L-L for 220/440V split-phase) 440 3 3 LL Red wires
460 (L-L, at point of use) 460 3 3 LL Red wires
480 (L-L for 480Y/277V 3-phase) 480 3 3 LL Red wires
600 (L-L 3-phase) not allowed No No No No No
690 (L-L 3-phase) not allowed No No No No No
* Nominal 254V source must operate normally at > 240V (95% of nominal)
** Maximum 480V per channel. 575Y/332V and 600Y/346V systems must use the 346 (L-N) configuration. 690Y/400V
systems must use the 346 (L-N) configuration.