Installation Instructions Bulletin 1608S i-Sense® Voltage Sag Detector Catalog Numbers: 1608S-3V480K, 1608S-6V480K
Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
Bulletin 1608S i-Sense® Installation Instructions Installation Pre-installation 1. Inspect for shipping damage 2. Record the i-Sense® serial number * 3. Register the i-Sense at www.igrid.com* 4. Configure the i-Sense hardware for the service voltage * 5. Configure communications software using the Ethernet port.
Bulletin 1608S i-Sense® Installation Instructions 1. Select your voltage configuration from Table 2and follow the instructions in the corresponding wiring diagram from Table 1. L e f t 2. Use the appropriate wiring diagram and jumper wire positions. The i-Sense is shipped with jumper wires in the LL configuration. The LL and LN diagrams are also shown inside the i-Sense cover. Move or remove jumper wires as needed.
Bulletin 1608S i-Sense® Installation Instructions Nominal Voltage Configurations Table 2 - Nominal Voltage Configurations.
Bulletin 1608S i-Sense® Installation Instructions Communications Connections 1. Remove left side cover (two Phillips-head screws, top and bottom) 2. Conduit entry: top or bottom. 3. Install appropriate communications cable(s)* * For more information, please refer to Rockwell Automation Publication 1608S-UM001-EN-P 8P8C (RJ45) modular Ethernet cable. Pass the Ethernet cable through the included RF filter core, and close the core securely, as shown in Figure 1.
Bulletin 1608S i-Sense® Installation Instructions Technical Specifications Electrical Nominal Voltage User-selectable, 100V-480Vrms, 1-Phase or 3-Phase Immune to voltage fluctuation up to ±10% of nominal and transient over voltages typically present on mains supply (impulse withstand Category II of IEC 60364-4-443) Frequency 45...65 Hz, auto-sensing Measurement inputs 1 to 3 channels, Cat. No.: 1068S-3V480K (3-channel) Up to 6 channels, Cat. No.
Bulletin 1608S i-Sense® Installation Instructions Standards Compliance and Certifications cTUVus (OSHA NRTL) listed Tested to UL and CSA safety standards CE mark (Safety and EMC) RoHS compliant FCC part 68 (Telephone Equipment) FCC part 15 (Emissions) Industry Canada CS-03 (Telephone Equipment) European Union CTR21 (Telephone Equipment) Compliance Information • • • • • • • • FCC PART 68 • This equipment complies with Part 68 of the FCC rules and the requirements adapted by the ACTA.
Bulletin 1608S i-Sense® Installation Instructions • The Telephone Consumer Protection Act of 1991 makes it unlawful for any person to use a computer or other electronic device including fax machines, to send any message unless such message clearly contains in a margin at the top or bottom of each transmitted page or on the first page of transmission, the date and time it was sent and an identification of the business or other entity, or other individual sending the message and the telephone number of the m
Bulletin 1608S i-Sense® Installation Instructions • This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. This equipment generates, uses, and can radiate radio-frequency energy. If not installed and used in accordance with the instructions, it can cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.