User Manual, 25 and 50 A

36 Rockwell Automation Publication 1608P-UM001A-EN-P - July 2013
Chapter 7 Specifications and Dimensions
Heat Dissipation
Approximate Dimensions
Dimensions are shown in inches (millimeters). Dimensions are not intended to be used for
manufacturing purposes.
Rating
(A)
Heat Loss (J) Heat Loss (Btu/h) Efficiency (%)
Standard Run-time (SR)
25 280 957 97.8%
50 350 1196 97.2%
Extended Run-time (ER)
25 420 1435 98.2%
50 560 1913 97.7%
Rating
(A)
H x W x D
in. [mm]
Weight
lbs.[kg]
Standard Run-time (SR)
25 32 x 26 x 14 [813 x 660 x 356] 277 [126]
50 38 x 38 x 14 [965 x 965 x 356] 330 [150]
Extended Run-time (ER)
Voltage independent; may be either 3 or 4 wire
25 32 x 26 x 14 [813 x 660 x 356] 307 [140]