User Manual, 25 and 50 A

Rockwell Automation Publication 1608P-UM001A-EN-P - July 2013 13
Installation Chapter 2
Table 2 - ProDySC 25 Amp Power Cable Terminations
Table 3 - ProDySC 50Amp Power Cable Terminations
3 Wire with a Ground
Terminal
Connection
Function Terminal Marking
Wire Range
AWG (mm²)
Torque lb-in
(Nm)
AC Input Phase A, B, C L1, L2, L3 24- 8 (0.5-6) 7.1- 8.9
(0.8-1)
Ground ¼-20 Stud 65
(7.3)
AC Output Phase A, B, C X1, X2, X3 24-8 (0.5-6) 7.1- 8.9
(0.8-1)
Ground ¼-20 Stud 65
(7.3)
4 Wire with a Ground
AC Input Phase A, B, C L1, L2, L3 24- 8 (0.5-6) 7.1- 8.9
(0.8-1)
Ground ¼-20 Stud 65
(7.3)
Neutral N 10-0 (1-35) 24.9- 26.7
(2.8-3)
AC Output Phase A, B, C X1, X2, X3 24- 8 (0.5-6) 7.1- 8.9
(0.8-1)
Neutral N 10-0 (1-35) 24.9- 26.7
(2.8-3)
Ground ¼-20 Stud 65
(7.3)
3 Wire with a Ground
Terminal
Connection
Function Terminal Marking
Wire Range
AWG (mm²)
Torque lb-in
(Nm)
AC Input
Phase A, B, C L1, L2, L3 10-0 (1-35)
24.9-26.7
(2.8-3)
Ground ¼-20 Stud 65 (7.3)
AC Output
Phase A, B, C, X1, X2, X3 10-0 (1-35)
24.9-26.7
(2.8-3)
Ground ¼-20 Stud 65 (7.3)
4 Wire with a Ground
AC Input
Phase A, B, C
and Neutral
L1, L2, L3, N 10-0 (1-35)
24.9-26.7
(2.8-3)
Ground ¼-20 Stud 65 (7.3)
AC Output
Phase A, B, C
and Neutral
X1, X2, X3, N 10-0 (1-35)
24.9-26.7
(2.8-3)
Ground ¼-20 Stud 65 (7.3)
WARNING: The ProDySC must be safety-grounded according to the National
Code. In addition, all local, state, and federal regulations applicable to the
installation of electrical systems as well as accident prevention regulations
must be strictly observed.