User Manual, 200 A Owner manual

Rockwell Automation Publication 1608P-UM003A-EN-P - September 2013 13
Chapter 3
Communications
Both dry contacts (relays) that indicate status and a Serial Communications Port
(RS-232) are available for monitoring the ProDySC.
Dry Contacts
Three relay contacts indicate ProDySC status. The contacts are form A and close
upon occurrence of the named event: (a) any SAG EVENT, when rms input
voltage drops below 88.5% of rated value; (b) OUTPUT OK, when output
voltage remains between 87% and 110%; and (c) a system ALARM event. The
relay contact ratings are 24V at 1A.
For access, remove the small metal cover from the top of the ProDySC
(See Figure 6
).
All wiring is to be Class 2, limited to 24 Volts, AC or DC.
Acceptable wire gauges range from 24AWG to 12AWG (0.205-2.5mm2).
Torque connections to 5.0 lb-in (0.6 N-m).
For permanent installation of communications conductors, a standard
conduit knockout is located on the cabinet top (See Figure 2
).
Figure 6 - Access Cover Location