Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013 9
Installation Chapter 2
NOTICE: The 1608P bypass switch contacts are designed to make-before-break and will not
disrupt power to the load during any mode transitions. The switch has lockout/tagout (LOTO)
provisions.
Circuit Breaker
Recommendations
Branch circuit protection upstream of the ProDySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in
Table 1
. Branch circuit protection rated less than the ProDySC current rating
may result in nuisance tripping.
Table 1 - Recommended Branch Circuit Protection
Electrical Terminations
The ProDySC must be installed by a qualified electrician. The ProDySC input
(line) and output (load) terminals are located behind the top door, as shown in
Figure 3
. Terminal details are shown in Figure 7 on page 13.
Figure 3 - Input/Output Terminal Location
ProDySC Rating Max. MCCB Rating
100 A 125 A
110 A 150 A
INPUT/OUTPUT
NEUTRAL
BUS
GROUND
BUS