User Manual, 100/110 A User Manual

Rockwell Automation Publication 1608P-UM002A-EN-P - July 2013 25
Display Screen Chapter 5
System Events The ProDySC tracks all operational events which are classified into five groups
based on severity.
Table 6 - System Event Description
System Event Log
The "System Event Log" screen displays a list of the last 40 system events in
chronological order (See Figure 21
). Reach this screen by pressing "SYSTEM
EVENTS" on the "HOME" screen.
Figure 21 - System Event Log
Table 7 - System Event Log Description
Description Function
Informational Purely informational. No action is required.
Auto-Resetting The PRODySC will reset within 60 seconds. No user action is required.
User Attention
User action may be required to correct a problem. The PRODySC will reset 60
seconds after the error condition is corrected.
Manual-Reset
For system events that force an automatic transfer to mechanical bypass, a
manual reset of the DySC system will be required.
Call Service
For events classified as Call Service, factory trained service support will be
required. Contact SoftSwitching Technologies support.
Description Function
# Unique ID (0-39) to identify the system event (unique within the list)
Time Start time of the system event
Name Short name of the system event.
Severity Severity of the system event
Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional detail about the system event.