Installation Instructions, 25 and 50 A Instruction Manual
16 Rockwell Automation Publication 1608P-IN001B-EN-P - May 2014
Chapter 3 Communications
Serial Communications Port
The ProDySC serial port is a DE-9 female connector. The pin-out follows
standard RS-232 protocol: pin 2 is RxD, pin 3 is TxD and pin 5 is common
(return). All other pins are unused. Contacts are galvanically isolated from the
system power and grounds.
• Protection: The RS-232 port is ESD-protected to 15kV
• Protocol: 57.6k bps, 8 data bits, one stop bit, no parity, flow control off
• Data packets are SLIP encoded (with 2 byte length field)
• Data accessible through this port includes line and load voltages, line and
load currents, status, and event and diagnostic logs.
• Consult Rockwell Automation technical support for specifications to the
ProDySC SLIP protocol.
Figure 9 - Serial Communications Port