Chapter 2 Operation
Communications
Two relay contacts indicate MiniDySC status. The contacts are form A and close
upon occurrence of the named event: (a) OUTPUT OK, when output voltage
remains between 87…110% of nominal value; and (b) a system ALARM event.
The relay contact ratings are 24VDC at 1A. The communications wiring area
detail is shown in Figure 11
. A barrier plate prevents contact between
communications wiring and power wiring.