User Manual, 800 Amp - 208V Owner's manual

Rockwell Automation Publication 1608M-UM003A-EN-P - December 2013 15
Installation Chapter 2
Figure 7 - Mechanical interconnections between 800A MegaDySC Module, Automatic Bypass
Switchboard, and ER Module for BTB layout
MegaDySC Floor Mounting
The MegaDySC system is floor-mounted, and should be secured using the
0.63in. (15.9 mm) diameter mounting holes provided along the bottom
channels. The system should be secured to the floor in the locations indicated in
Figure 8
, Figure 9, and Figure 10.
The minimum number of anchor bolts is 10 for SR systems and 14 for ER
systems:
Automatic Bypass Switchboard: 4 places (one in each corner)
800 A MegaDySC Module: 6 places (one in each corner and one in each
end of the middle rail)
ER Module: 4 places (one in each corner)