Display Screen Chapter 6
System Events
The MegaDySC tracks all operational alarms. These “System Events” are
classified into five groups based on severity, as listed in the following table.
System Event Log
The “System Event Log” screen displays a list of the last 40 system faults in
chronological order (See Figure 16
). You can access this screen by pressing the
“System Events button in the menu.
Figure 16 - System Event Log
The left side of the screen contains the list of system events, which are identified
by these fields:
Use the up/down arrows to navigate through the list. Detail for the currently
selected event is shown to the right of the list.
Severity Description
Informational Purely informational. No action is required.
Auto-Resetting The DySC will reset within 60 seconds. No user action is required.
User Attention
User action may be required to correct a problem. The DySC will reset 60
seconds after the error condition is corrected.
Manual-Reset
For system events that force an automatic transfer to mechanical bypass, a
manual reset of the DySC system will be required.
Call Service
For events classified as Call Service, factory trained service support will be
required.
Description Function
# Unique ID within the list identifying each system event
Time Start time of the fault.
Name Name and description of the alarm.