User Manual, 800 - 2400 A User guide

Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013 27
Display Screen Chapter 6
System Status
The “System Status” screen displays the real-time overall system status (See
Table 5
). You can access this screen by pressing the “System Status” button in the
menu.
Table 5 - System Status
Note: You can toggle between the two screens in Figure 10 by pressing “System
Summary” and “Line & Load Waveforms” on the left side of the screen.
Figure 10 - System Status Screen
on
p
Item Description Function
System Status
Overall system status including: status, availability to correct sags, and internal cabinet temperature.
Voltage, current, frequency, and static switch temperature are displayed for all phases. The percentage displayed following the voltage and
current is the percent of nominal value for the MegaDySC unit. Nominal values are listed on the “View Model Information” screen.
Cabinet Layout The system component cabinets are displayed; press a cabinet for more detail.
Waveforms Real-time waveform capture; line voltage, load voltage, or load current can be selected for display.