User Manual, 208 Volt, One Second Extended Runt User Manual

10 Rockwell Automation Publication 1608M-UM004A-EN-P - April 2014
Chapter 2 Installation
To attach the MegaDySC module to the ER module, install the four (4) sets of
3/8-16 interconnection bolts along the front of the cabinets, as shown in detail B
of Figure 2
. Tighten each bolt to 20 N-m [180 in-lb].
Finally, after all interconnection hardware is installed; tighten the anchor bolt
connections to the torque specified by the anchor manufacturer.
Figure 2 - Mechanical interconnections between MegaDySC Module, Automatic Bypass
Switchboard, and ER Module
MegaDySC Floor Mounting
The MegaDySC system is floor-mounted, and should be secured using the
0.63in. (15.9 mm) diameter mounting holes provided along the bottom
channels. The system should be secured to the floor in the locations indicated in
Figure 3
. The minimum number of anchor bolts is 14:
Automatic Bypass Switchboard: 4 places (one in each corner)
MegaDySC Module: 6 places (one in each corner and one in each end of
the middle rail)
ER Module: 4 places (one in each corner)