Chapter 3
Communications
Remote Diagnostics and
Remote Bypass
Relay dry contacts are available for remote monitoring of the state of the Bypass
Circuit Breaker CBB and the Input Circuit Breaker CBI shunt-trip condition
(See Figure 7
). In addition, a customer-supplied relay may be used to remotely
command a Seamless Bypass operation, as described in Publication 1608M-
UM001A-EN-P. These functions are available from terminal block TB1 located
in the upper compartment of the bypass switchboard. See Figure 9
and Figure 6
for recommended conduit entry location.
Figure 7 - Schematic Diagram - Status Relay Contacts
CBB Contacts
(Bypass Circuit Breaker)
"Normal" position for the Bypass Breaker is defined as the breaker being OFF, or
Open. As such, the Normally-Open contacts are open when the Breaker is open;
the Normally-Closed contacts will open when the breaker is closed.
Example: Normal run: CBB will be Open; therefore TB1/11B will be electrically
connected to TB1/10B.
K1
5
13
6
2
4
78
CBB
N/C
CBB1
N/O
TB1
terminal block
NC
1
A
C
2
A
NO
3
A
NC
1B
C
2B
NO
3B
NC
4
A
C
5
A
NO
6
A
NC
4B
C
5B
NO
6B
.
7B
.
8B
.
9B
NC
10B
C
11B
NO
12B
unused
7
A
unused
8
A
unused
9
A
NC
10A
C
11A
NO
12A
NC
13B
C
14B
NO
15B
NC
13A
C
14A
NO
15A
Customer-Supplied Contact:
Close to command
Seamless Bypass