User Manual, 200 A Owner's manual
33 Rockwell Automation Publication 1608P-UM004A-EN-P - September 2013
Chapter 6 Maintenance
36
COM_VER
Start-Up Test: Communication
Compatibility Mismatch
Call Service Unit
Firmware communication compatibility problem detected during start-up
test.
Call service.
37
CNFG_TO
Start-Up Test: Controller Configuration
Timeout
Call Service Unit Controller communication problem detected during start-up test. Call service.
38
CNFG_ERR
Start-Up Test: Controller Configuration
Mismatch
Call Service Unit Controller firmware configuration problem detected during start-up test. Call service.
39
FIRM_TO
Start-Up Test: Controller Firmware
Check Timeout
Call Service Unit Controller communication problem detected during start-up test. Call service.
40
FIRM_DIFF
Start-Up Test: Controller Firmware
Revision Mismatch
Call Service Unit Controller firmware revision mismatch detected during start-up test. Call service.
41
SRL_TO
Start-Up Test: Controller Serial Number
Check Timeout
Call Service Unit Controller communication problem detected during start-up test. Call service.
42
SRL_DIFF Start-Up Test: Serial Number Mismatch Informational Unit Controller serial number mismatch detected during start-up test. No action needed.
44
T_INV_TO Inverter Test Timeout Call Service Unit Phase control board failed to respond to Comm board's Inverter test. Call service.
46 DOOR_OPEN DySC Cabinet Door Open Manual Reset Unit DySC door was opened. Mechanical bypass commanded. Close door. Manually reset DySC.
47 CRIT_OT Critical Over-Temperature Manual Reset Unit
Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.
Verify ambient temperature is within DySC specification.
Check for damaged fans. Check for dirty or obstructed air filters.
Manually reset DySC.
48 FUSE_OPEN Fuse Open Call Service Unit One of the DySC fuses was detected open. Mechanical bypass commanded. Call service.
49 OPEN_SCR_A Open SCR Phase A Call Service Static Switch The SCR on the phase A module was detected open. Call service.
50 OPEN_SCR_B Open SCR Phase B Call Service Static Switch The SCR on the phase B module was detected open. Call service.
51 OPEN_SCR_C Open SCR Phase C Call Service Static Switch The SCR on the phase C module was detected open. Call service.
53 DYN_BRAKE Dynamic Brake Error Call Service Unit A problem was detected with the DySC dynamic brake controller. Call service.
58 PLC_ERR Programmable Logic Controller Error Call Service PLC PLC error detected. Call service.
59 PLC_ST_MM
Programmable Logic Controller State
Mismatch
Call Service Unit PLC feedback error detected. Call service.
Event
Code
Code Name Full Name Severity Area Event Description Event Resolution