Reference Manual

All parameters are specified at 24V, 80A output current, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM011A-EN-P — February 2014 11
Bulletin 1606 Switched Mode Power Supplies
11. Protection Features
Output over-current protection not included
Reverse input polarity
protection
included Unit does not start when input voltage is reversed.
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.6mm e.g. screws, small parts
Over-temperature protection not included
Input transient protection not included
Output transient protection included See EMC section.
Internal input fuse not included
12. Safety Features
Input / output separation no galvanic separation Mosfet between input and output
Class of protection III PE (Protective Earth) or chassis connection not required
PE resistance < 0.1Ohm between housing and chassis-ground terminal
13. Dielectric Strength
The input and output voltages have the same reference, are oating and have no ohmic connection to the ground.
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the eld using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect input/output
terminals together before conducting the test.
When testing, set the cut-off current settings to the value in the table below.
Fig. 13-1 Dielectric strength
A
Type test 60s 500Vac
Factory test 5s 500Vac
Field test 5s 500Vac
Cut-off current setting > 2mA
A
Chassis
In- / Output
-
+