User Manual
1606-XLSRED Decoupling Module Instruction Manual / Bedienungsanleitung Entkopplungsmodul
1606-XLERED Redundancy Module Instruction Manual / Bedienungsanleitung Redundanzmodul
Product Description
The reliability of the DC voltages can be increased by using redundant systems. To achieve
redundancy, one extra power supply must be installed in order to deliver the required current in
case one power supply in the system fails. Each individual power supply must be isolated from the
others with diodes or mosfets. Redundancy modules have such components included and are
equipped with two input and one output channels. They can be used to build 1+1 and N+1
redundant systems.
The 1606-XLSRED and 1606-XLERED are redundancy modules for currents up to 20A and utilize
diodes to isolate the two inputs. The 1606-XLERED has a monitoring circuitry included. LEDs and
relay contacts signal when one of the two input voltages is not in range due to a non-functioning or
disconnected power supply. The 1606-XLSRED has no monitoring circuitry included and is the
perfect fit when the power supply itself is already equipped with a DC-OK contact. The 1606-
XLSRED40 and 1606-XLSRED80 are high-current redundancy modules for currents up to 40A
and 80A. The novelty of these redundancy modules is the utilization of mosfets instead of diodes
for isolating the two input channels. This reduces the heat generation and the voltage drop
between input and output.
A
ll redundancy modules do not require an additional auxiliary voltage and are self-sufficient even
in case of a short circuit across the output.
Gerätebeschreibung
Die Zuverlässigkeit von DC-Spannungen kann durch redundante Systeme erhöht werden. Um
eine Redundanz zu erreichen, muss ein zusätzliches Gerät in „Reserve“ installiert werden, das
dann den nötigen Laststrom zur Verfügung stellt, wenn ein Gerät im System ausfällt. Die
einzelnen Geräte müssen mittels Dioden oder Mosfets entkoppelt sein. Diese Bauteile sind in den
Redundanzmodulen integriert. Redundanzmodule haben zwei Eingänge und einen Ausgang und
können zum Aufbau von N+1 oder 1+1 redundanten Systemen verwendet werden.
Die 1606-XLSRED und 1606-XLERED Redundanzmodule sind für Ströme bis 20A geeignet und
verwenden Dioden zur Entkopplung. Das 1606-XLERED hat eine Überwachung der
Eingangsspannungen eingebaut. LEDs und Relaiskontakte melden, wenn eine der beiden
Eingangsspannungen unterhalb des zulässigen Bereiches ist. Das 1606-XLSRED hat keine
Überwachungsfunktion eingebaut und kann verwendet werden, wenn die Stromversorgung selbst
bereits mit einem DC-OK Signal ausgestattet ist. 1606-XLSRED40 und 1606-XLSRED80 sind
Redundanzmodule für 40A und 80A Ausgangsstrom. Das Novum dieser Module sind die Mosfets
anstelle von Dioden zur Entkopplung der beiden Eingänge. Damit werden die Wärmeentwicklung
und der Spannungsabfall zwischen Eingang und Ausgang deutlich reduziert.
A
lle Redundanzmodule benötigen keine zusätzliche Hilfsspannung und versorgen sich selbst,
auch im Falle eines Kurzschlusses am Ausgang.
Technical Data
1)
Technische Daten
1)
1606-XLSRED 1606-XLERED 1606-XLSRED40 1606-XLSRED80
Input Voltage Eingangsspannung nom. DC 12-48V
±25%
DC 24-48V
±25%
DC 24-28V
±30%
DC 24-28V
±30%
Input Voltage Range Eingangsspannungsbereich - 9-60Vdc 18-60Vdc 16.8-36.4Vdc 16.8-36.4Vdc
Output Current
2)
Normal Mode Ausgangsstrom
2)
Normalbetrieb nom. 20A 20A 40A 80A
Overload, Short-circuit Überlast, Kurzschluss max. 25A
3)
25A
3)
65A
3)
130A
3)
Input Current
2)
1+1 Redundancy Mode Eingangsstrom
2)
1+1 Redundanz Modus nom. 2x 12.5A 2x 12.5A 2x 20A 2x 40A
N+1 Redundancy Mode N+1 Redundanz Modus nom. 2x 10A 2x 10A 2x 20A 2x 40A
Peak Input Current (per input) Eingangsspitzenstrom (pro Eingang) max. 150A for 10ms 150A for 10ms 1000A for 1ms 1500A for 1ms
Reverse Current
4)
(per input) Rückwärtsstromstrom
4)
(pro Eingang) max. 2mA 2mA 1mA 1mA
Decoupling Element Entkopplungselement - Diode Diode Mosfet Mosfet
Voltage Drop
5)
(Input to Output) Spannungsabfall
5)
(Eingang zu Ausgang) typ. 850mV 850mV 140mV 95mV
Power Losses
5)
at full load Verlustleistung
5)
bei Volllast typ. 17W 18W 6.3W 8.3W
at no load im Leerlauf typ. 0W 1W 0.7W 0.7W
Low-Input-Voltage Alarm Contacts Eingangsspannungsüberwachungsrelais - no / nein yes / ja no / nein no / nein
Alarm threshold level (Alarm Meldeschwelle) nom. - 21.5V (±0.5V) - -
Operational Temperature Range Betriebstemperaturbereich nom. -40°C - +70°C -40°C - +70°C -40°C - +70°C -40°C - +70°C
Output Derating Ausgangsstromrücknahme +60°C to +70°C 0.5A/°C 0.5A/°C 0A/°C 0A/°C
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C -40°C - +85°C -40°C - +85°C
Humidity
6)
Feuchte
6)
IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H.
Vibration Schwingen IEC 60068-2-6 2g 2g 2g 2g
Shock Schocken IEC 60068-2-27 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms
Degree of Pollution (non-conductive) Verschmutzungsgrad (nicht leitend) EN 50178 / IEC 62103 2 2 2 2
Degree of Protection Schutzart EN 60529 IP20 IP20 IP20 IP20
Class of Protection Schutzklasse IEC 61140 III
7)
III
7)
III
7)
III
7)
Over-Temperature Protection Übertemperaturschutz OTP no / nein no / nein no / nein no / nein
Reverse Input Polarity Protection Eingangsverpolschutz - yes / ja yes / ja yes / ja yes / ja
Penetration Protection Fremdkörper Eindringschutz max. 3.5mm 3.5mm 3.5mm 3.5mm
Return Voltage Resistance
8)
Rückspeisefestigkeit
8)
max. 200Vdc 200Vdc 40Vdc 40Vdc
Isolation Against Housing Isolationsfestigkeit gegen Gehäuse min. 500Vac, 5MOhm 500Vac, 5MOhm 500Vac, 5MOhm 500Vac, 5MOhm
Quick-Connect Spring-Clamp Terminals Schnellanschluss Federkraftklemmen - yes / ja no / nein no / nein no / nein
Screw Terminals Schraubklemmen - yes / ja no / nein yes / ja yes / ja
Dimensions
9)
(WxHxD) Abmessungen
9)
(BxHxT) nom. 32x124x102mm 32x124x117mm 36x124x127mm 46x124x127mm
Weight Gewicht max. 290g, 0.64lb 350g, 0.77lb 340g, 0.75lb 440g, 0.97lb
Approvals Zulassungen - 10) 10) 10) 10)
1) All parameters are specified at 24Vdc input voltage, nominal output current, 25°C ambient
and after a 5 minutes run-in time unless otherwise noted.
2) 50% higher currents up to 5s are allowed.
1+1 and N+1 Redundancy modes are explained in figures 1 to 2.
3) Ensure that the continuous output current does not exceed this value. Check the short-circuit
current of power sources. If both power sources can deliver higher currents, use an
appropriate fuse on the output.
4) Over the entire temperature range.
5) At nominal output current and symmetrical input currents. See figure 6 to 8.
6) Do not energize while condensation is present.
7) PE (Ground) connection optional but not required.
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the
redundancy module. The figure represents the maximum allowed feed back voltage.
9) Depth without DIN-rail and connection terminals.
10) See datasheet or markings on the unit.
1) Alle Werte gelten bei 24Vdc Eingangsspannung, Nennausgangsstrom, 25°C Umgebungs-
temperatur und nach einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist.
2) 50% höhere Ströme sind bis zu 5s erlaubt.
1+1 und N+1 Redundanzmodus sind in den Bildern 1 bis 2 erklärt.
3) Der Dauerausgangsstrom darf auch im Fehlerfall diesen Wert nicht überschreiten. Überprüfen
Sie auch den Ausgangsstrom bei Kurzschluss. Wenn beide Spannungsquellen zusammen
mehr Strom liefern können, ist eine geeignete Sicherung am Ausgang zu verwenden.
4) Über den gesamten Arbeitstemperaturbereich.
5) Bei Nennausgangsstrom und symmetrischen Eingangsströmen. Siehe auch Bilder 6 bis 8.
6) Nicht betreiben, solange das Gerät Kondensation aufweist.
7) PE Verbindung erlaubt, aber nicht erforderlich.
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des
Redundanzmoduls rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene und Anschlussklemmen.
10) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.
Fig. 1 / Bild 1
1+1 Redundancy / 1+1 Redundanz
Fig. 2 / Bild 2
N+1 Redundancy / N+1 Redundanz
AC
DC
AC
DC
Load
+
-
IN 1
OUT
IN 2
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
AC
DC
IN 1
OUT
IN 2 IN 1
OUT
IN 2 IN 1
OUT
IN 2
Load
+
-