All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM009A-EN-P — February 2014 19
Bulletin 1606 Switched Mode Power Supplies
17.9. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature.
Fig. 17-6
Mounting
Orientation A
(Standard
orientation)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
4
12
16
20A
50
8
Ambient Temperature
Fig. 17-7
Mounting
Orientation B
(Upside down)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
4
12
16
20A
50
8
Ambient Temperature
Fig. 17-8
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
4
12
16
20A
50
8
Ambient Temperature
Fig. 17-9
Mounting
Orientation D
(Horizontal cw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
4
12
16
20A
50
8
Ambient Temperature
Fig. 17-10
Mounting
Orientation E
(Horizontal ccw)
Redundancy
Module
INPUT
OUTPUT
Output Current
0
10 20 30 40
60°C
4
12
16
20A
50
8
Ambient Temperature