All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
8 Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 230V
Hold-up Time typ. 58ms at 48V, 10A, see Fig. 7-1
min. 47ms at 48V, 10A, see Fig. 7-1
typ. 30ms at 48V, 20A, see Fig. 7-1
min. 24ms at 48V, 20A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, denitions