All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.
12 Rockwell Automation Publication 1606-RM032A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
13. Lifetime Expectancy and MTBF
3AC 400V 3AC 480V
Calculated lifetime expectancy
*)
314 000h
*)
294 000h
*)
at 48V, 10A and 25°C
111 000h 104 000h at 48V, 10A and 40°C
179 000h
*)
174 000h
*)
at 48V, 20A and 25°C
63 000h 62 000h at 48V, 20A and 40°C
MTBF
**)
SN 29500, IEC 61709 375 000h 369 000h at 48V, 20A and 40°C
685 000h 678 000h at 48V, 20A and 25°C
MTBF
**)
MIL HDBK 217F 158 000h 157 000h at 48V, 20A and 40°C; Ground Benign GB40
211 000h 210 000h at 48V, 20A and 25°C; Ground Benign GB25
*) The calculated lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours and is calculated according
to the capacitor’s manufacturer specication. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15
years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF gure is a statistical representation of the likelihood of a device to fail. A MTBF gure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the eld. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
14. Functional Diagram
Fig. 14-1 Functional diagram
+
+
-
-
V
OUT
DC-ok
Contact
Output
Over-
Voltage
Protection
PFC
Converter
Input Fuses
Input Filter
Input Rectier
Inrush Limiter
Transient Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
LED
DC-ok
LED
L2
L3
L1
Single /
Parallel
Shut-
down
Input
Shut-
down
13
14
15
16
Event Datalogger