Reference Manual Instruction Manual

All parameters are specified at 24V, 40A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM029A-EN-P — April 2014 27
Bulletin 1606 Switched Mode Power Supplies
25.13. Mounting Orientations
Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a
limitation in the maximum allowed ambient temperature. The amount of reduction inuences the lifetime expectancy
of the power supply. Therefore, two different derating curves for continuous operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 25-6
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUTINPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
A
1
Ambient Temperature
Fig. 25-7
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUTINPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
A
2
Ambient Temperature
A
1
Fig. 25-8
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
Ambient Temperature
A
1
A
2
Fig. 25-9
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUTINPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
Ambient Temperature
A
1
A
2
Fig. 25-10
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
10
20
30
40A
50
Ambient Temperature
A
1
A
2