Reference Manual Owner manual

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
10 Rockwell Automation Publication 1606-RM017A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
event, the process is completed much faster since only the energy which was taken out of the battery needs to be
“relled”. For this reason, the buer time cannot be calculated using the Ah capacity value.
T
he equation “I x t” = capacity in Ah generally leads to incorrect results when the discharging current is higher than
C20 (discharging current for 20h). The battery datasheet needs to be studied and a determination of the expected
buer time can be made by following the example below:
Example how to determine the expected buer time for other battery types and battery sizes:
Step 1 Check the datasheet of the battery which is planned to be used and look for the discharging curve.
Sometimes, the individual discharging curves are marked with relative C-factors instead of current
values. This can easily be converted. Multiply the C-factor by the nominal battery capacity to obtain
the current value. E.g.: 0.6C on a 17Ah battery means 10.2A.
Fig. 9-2 Typical discharging of a typical 17Ah battery, curve taken from
a manufacturer’s datashet
Step 2 Determine the required battery current. Use Fig. 8-1 “Battery discharging current vs. output current” to
get the battery current.
Fig. 8-1 requires the average voltage on the battery terminals. Since there is a
voltage drop between the battery terminals and the battery input of the DC-UPS, it is recommended to
use the curve A or B for output currents > 3A or when using long battery cables. In all other situations,
use curve C.
Step 3 Use the determined current from Step 2 to nd the appropriate curve in Fig. 9-2. The buer time
(Discharging Time) can be found where this curve meets the dotted line. This is the point where the DC-
UPS stops buering due to the under-voltage lockout.
Step 4 Depending on Fig. 9-2, the buer time needs to be reduced to take into account aging eects or
Example:
Buer current is 24V 7.5A and a battery according to Fig. 9-2
is used. The cable between the battery and the DC-UPS
is 1m and has a cross-section of 2.5mm
2
. How much is the maximum achievable buer time?
Answer:
According to Fig. 8-1, the battery current is 18A. Curve A is used since the battery current is > 3A and the
length of the cable is one meter.
According to Fig. 9-2, a buer time (Discharging Time) of 30 minutes can be determined. It is recommended
to reduce this gure to approximately 24 minutes for a guaranteed value and to cover aging eects.
guaranteed values.