Reference Manual Instruction Manual
All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM044A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 100-240V Wide-range Input
Width only 60mm
Efciency up to 93.5%
150% (360W) Peak Load Capability
Easy Fuse Tripping due to High Overload Current
Active Power Factor Correction (PFC)
Negligible low Inrush Current Surge
Short-term Operation down to 60Vac and up to 300Vac
Full Power Between -25°C and +60°C
DC-OK Relay Contact
Quick-connect Spring-clamp Terminals
3 Year Warranty
Description
The most outstanding features of the 1606-XLS DIN
rail power supplies are their high efciency and small
sizes, which are achieved by a synchronous
rectication and further design innovations. The 1606-XLS
series is part of Rockwell Automation's family of power
supplies, existing alongside lower featured power supplies.
With short-term peak power capability of 150% and
built-in large sized output capacitors, these features
help start motors, charge capacitors and absorb reverse
energy and often allow a unit of a lower wattage class
to be used.
High immunity to transients and power surges as well as
low electromagnetic emission makes usage in nearly
every environment possible.
The integrated output power manager, a wide range
input voltage design and virtually no input inrush
current make installation and usage simple. Diagnostics
are easy due to the dry DC-ok contact, a green DC-ok
LED and red overload LED.
Unique quick-connect spring-clamp terminals allow a
safe and fast installation and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.
Specication Quick Reference
Output voltage DC 24V
Adjustment range 24 - 28V
Output current 10 – 9A continuous
15 – 13.5A for typ. 4s
Output power 240W continuous
360W for typ. 4s
Output ripple < 50mVpp 20Hz to 20MHz
Input voltage AC 100-240V ±15%
Mains frequency 50-60Hz ±6%
AC Input current 2.22 / 1.22A at 120 / 230Vac
Power factor 0.98 / 0.92 at 120 / 230Vac
AC Inrush current typ. 4 / 7A peak at 120 / 230Vac
Efciency 92.6 / 93.5% at 120 / 230Vac
Losses 19.1 / 16.7W at 120 / 230Vac
Temperature range -25°C to +70°C operational
Derating 6W/°C +60 to +70°C
Hold-up time typ. 27 / 28ms at 120 / 230Vac
Dimensions 60x124x117mm WxHxD
Catalog Numbers
Power Supply
1606-XLS240E
1606-XLS240E-D
1606-XLS240EA
1606-XLS240EC
24-28V Standard unit
Extended DC-input
ATEX approved unit
Conformal coated unit
Accessories 1606-XLB Wall mount bracket
1606-XLSRED Redundancy module
1606-XLSBUFFER24 Buffer module
Certication Marks
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
ATEX
II 3G Ex nAC II T4
Marine
EMC, LVD
GOST R
Marine RINA
C-Tick