Reference Manual

All parameters are specified at 24V, 10A output load and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current
2 Rockwell Automation Publication 1606-RM036A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
DC-UPS Control Unit
Requires Only One 12V Battery for a 24V Output
Stable Output Voltage in Buer Mode
Superior Battery Management for Longest Battery Life
Comprehensive Diagnostic and Monitoring Functions
Replace Battery Signal Included
Electronically Overload and Short Circuit Protected
50% Power Reserves
Selectable Buer Time Limiter
3 Year Warranty
1. Description
2. Specication Quick Reference
Input voltage nom. 24Vdc
range 22.5-30Vdc
Output current min.15A Normal mode
min. 10A Buer mode
Output voltage typ. 0.23V lower
as input voltage
Normal mode
22.25V Buer mode, 10A
Allowed batteries 3.9Ah to 40Ah VRLA lead acid
Temperature range -25 to +70°C Operational
Derating 0.43A/°C
+60°C to +70°C
normal mode
Dimensions 49x124x117mm WxHxD
Buer time (at 10A)
typ. 6’45” 7Ah battery module
typ. 55’ 26Ah batt. module
This uninterruptible power supply (UPS) controller
1606-XLS240-UPS is an addition to standard 24V
power supplies to bridge power failures or voltage
uctuations. Expensive downtimes, long restart
cycles and loss of data can be avoided.
The DC-UPS includes a professional battery
management system which charges and monitors
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.
A unique feature of the 1606-XLS240-UPS is that only
one 12V battery is required to buer the 24V output.
This makes matching batteries unnecessary and
allows a precise battery charging and testing.
The 1606-XLS240-UPS requires one external 12V battery
for which two preassembled battery modules
are available: a lightweight 7Ah battery that can be
mounted on the DIN rail and a 26Ah module that
can be panel-mounted for longer buer times.
In addition to the 1606-XLS240-UPS, the
1606-XLS240-UPSC UPS includes the same controller
with an integrated 5Ah battery.
Typical setup of a DC-UPS system with the 1606-XLS240-UPS:
24V
Power
Supply
12V
Battery
24V
DC-UPS
24V
Load
AC DC
e.g.: PLC
3. Catalog Numbers
4. Certication Marks
DC-UPS
1606-XLS240-UPS
Standard controller
Accessories 1606-XLSBATASSY1 Battery module 12V 7Ah
1606-XLSBATBR1 Mounting kit w/o battery
IND. CONT. E
Q.
UL 508
UL 60950-1
Class I Div 2
1606-XLSBATASSY2 Battery module 12V 26Ah
1606-XLSBATBR2
Mounting kit w/o battery
1606-XLB
Panel/Wall mount bracket
EMC, LVD
GL
Marine
GOST R
C-Tick
Marine RINA